What is the Number of Samples Locations Calculations Readings for ISO14644?
The number of sample locations required to verify compliance with ISO 14644-1 (Air Cleanliness Classification by Particle Concentration) is determined by the size of the cleanroom or controlled area. ISO 14644 specifies a formula and provides tables to calculate the number of sampling locations based on the room’s area.
What is the Number of Samples Locations Calculations Readings for ISO14644?
By Ashraf Almuhtaseb | Data Center Technical Cleaning Expert | idata.center
The number of sample locations required to verify compliance with ISO 14644-1 (Air Cleanliness Classification by Particle Concentration) is determined by the size of the cleanroom or controlled area. ISO 14644 specifies a formula and provides tables to calculate the number of sampling locations based on the room’s area.
Calculation for the Number of Sample Locations
The number of sample locations is calculated using the formula:
𝑁𝐿=27× (𝐴 𝑚² ÷ 1000)
Where:
NL = Number of sample locations (rounded up to the next whole number)
A = Area of the cleanroom or zone in square meters (m²)
Simplified Table of Sample Locations
Below is a quick reference for typical cleanroom sizes:
Room Area (m²)
Minimum Sample Locations
2𝑚² = 2 readings
4𝑚² = 2 readings
10𝑚² = 3 readings
20𝑚² = 5 readings
50𝑚² = 8 readings
100𝑚² = 10 readings
500𝑚² = 23 readings
1000𝑚² = 32 readings
Larger than 1000 𝑚² = Use this formula (𝑁𝐿=27× (𝐴 𝑚² ÷ 1000) )
This table is a suggested number of samples per area; you can take more samples than suggested, and taking fewer is not recommended.
Sampling Procedure
A- Particle Measurement:
Measure particle concentration at each sampling location for the required particle sizes (e.g., 0.1 µm, 0.5 µm).
Use particle counters that comply with ISO 21501-4 standards.
B- Duration of Sampling:
The volume of air sampled at each location must be sufficient to detect the required number of particles based on the cleanroom classification.
C- Uniform Distribution:
Sampling points should be evenly distributed across the room, avoiding clustered locations unless local contamination sources are expected.
About the Author
Ashraf Almuhtaseb is a Data Center Technical Cleaning Expert with over 9 years of specialized experience since 2017. He is the only independent professional in the MENA region — and one of very few globally — publishing dedicated, in-depth technical knowledge on data center cleaning standards, contamination control, and ISO 14644 compliance. Visit idata.center for more articles, guides, and resources.